After 4B products have been installed by a qualified electrician, 4B's commissioning service is available to inspect and |
|
|
certify proper installation of our sensors and control units prior to operation. A brief overview of the service is listed |
|
|
below - |
|
|
|
|
|
|
|
General: |
|
|
• All rigid and flexible conduits inspected for: cracks, breaks, tightness of connections, and suitability for purpose. |
|
|
• All wiring inspected for: ground faults, shorts, suitability for purpose. |
|
|
• All sensors and controls inspected for correct installation, and wiring to National Electrical Code (NEC) standards. |
|
|
• All sensors and controls inspected for any signs of damage, and tested to insure proper working order. |
|
|
• Detailed written inspection and testing report with any recommendations given to client. |
|
|
|
|
|
|
|
Touchswitches™: |
|
|
• Sensors are removed from their location to ensure that they were centered on the belt. |
|
|
• Each Touchswitch is physically inspected for damage and wear. |
|
|
• Touchswitch LED and alarm contacts are tested. |
|
|
• Wire terminations are inspected. |
|
|
|
|
|
|
|
Temperature Sensors: |
|
|
• All sensors are inspected and resistance is checked. |
|
|
• Sensors are also checked for correct identification, location and sensor type. |
|
|
• Freeze spray is used to ensure that the sensor displays a change in temperature, or the ADB sensor tester is used |
|
|
to heat up the sensor to the alarm / trip point. |
|
|
• Wire terminations are inspected. |
|
|
|
|
|
|
|
Speed Switches: |
|
|
• All speed switches are checked for proper installation. |
|
|
• Sensors are checked for proper underspeed alarm and shutdown set points using 4B's SpeedMaster™. |
|
|
• Wire terminations are inspected. |
|
|
|
|
|
|
|
Warning: 4B recommends that all sensors are wired to provide automatic shutdown of monitored equipment, when a |
|
|
hazardous condition is detected. |
|
|
|
|
|
|